ORVALDI VR6K, VR10K online 2U LCD

Seria: On-line

With true double-conversion design, VR 6-10K series provides powerful and overall protection to your sensitive devices. It can accept wider input voltage for harsh environment. It's perfect protection for your precious servers and workstations.

Výrobce: ORVALDI
Kód produktu: VGAR6K, 10K
ORVALDI VR6K, VR10K online 2U LCD

Charakteristický:

True double-conversion

  • Microprocessor control optimizes reliability
  • Output power factor 1
  • Input power factor correction
  • Wide input voltage (110V-300V)
  • 50/60Hz Frequency converter mode
  • ECO mode for energy saving
  • Emergency power off (EPO) function
  • Built-in over voltage cut-off protection and surge immunity by MOV for full-time equipment protection
  • High power factor charger up to 1000W capacity with very low ripple current when charging battery
  • Lowe input THDi to reduce power system pollution
  • Adjustable charging current via LCD panel
  • Smart battery charger design to optimize battery performance
  • Generator compatible
  • Optional external SNMP slot

Seznam aplikací:

sensitive lab devices

automatics

controll

servers

 

Technická data:

Model ORVALDI 6K (L) RT ORVALDI 10K (L) RT
PHASE 1 phase in/ 1 phase out
CAPACITY 6000 VA/6000 W 10000 VA/10000 W
INPUT
Nominal Voltage 208/220/230/240 VAC
Voltage Range

110-300 VAC @ 0~60% load; 140-300 VAC @ 60~80 % load; 176-300 VAC @ 80~100 % load

Frequency Range 46 ~54 Hz or 56~64 Hz
Phase Single phase with ground
Power Factor ≧ 0.99 @ 100% Load
THDi ≦ 4% @100% load; <6% @ 50% load
OUTPUT
Output Voltage 208*/220/230/240 VAC 208*/220/230/240 VAC
AC Voltage Regulation (Batt. Mode) ± 1%
Frequency Range (Synchronized Range) 46~54 Hz or 56~64 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
Current Crest Ratio 3:1 (max.)
Harmonic Distortion ≦1.5% THD (Linear Load), ≦ 7 % THD (Non-linear Load)
Transfer Time AC Mode to Batt. Mode zero
Inverter to Bypass zero
Waveform (Batt. Mode) Pure Sinewave
Overload AC Mode 100%~110%: 10 min; 110%~130%: 1 min; >130%: 1 sec
Battery Mode 100%~110%: 30 sec; 110%~130%: 10 sec; >130%: 1 sec
EFFICIENCY
AC Mode 94% 94%
Battery Mode 91% 91%
BATTERY
Standard Model Battery Type 12V/7 Ah 12V/ 9Ah
Numbers    
Typical Recharge Time 9 hours recover to 90% capacity
Charging Current (Max.) 1.0A
Charging Voltage 218.4 VDC ±1%
Long-run Model Battery Type Depending on applications
Numbers 16-20**
Charging Current (Max.) 4.0A
Charging Voltage (13.65 VDC x battery number) ± 1%
INDICATORS
LCD Panel UPS status, load level, battery level, input/output voltage, discharge timer, and fault conditions
ALARM
Battery Mode Sounding every 4 seconds
Low Battery Sounding every 2 seconds
Overload Sounding twice every second
Fault Continuously sounding
PHYSICAL
Standard Model Dimension, DxWxH (mm) UPS Unit: 600x438x88 [2U]; Battery Pack: 695x438x88[2U] UPS Unit: 600x438x88 [2U]; Battery Pack:695x438x88[2U]
Net Weight (kgs) UPS Unit: 15; Battery Pack: 48 UPS Unit:18; Battery Pack: 48
Long-run Model Dimension, DxWxH (mm) 600x438x88 [2U] 600x438x88[2U]
Net Weight (kgs) 15 18
ENVIRONMENT
Humidity 20-90 % RH @ 0- 40°C (Non-condensing)
Noise Level Less than 55dB@1Meter Less than 58dB@1Meter
MANAGEMENT
Smart RS-232/USB Supports Windows 2000/2003/XP/Vista/2008, Windows 7/8, Linux, and MAC
Optional SNMP Power management from SNMP manager and web browser
 
* Derate capacity to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208 VAC.
** When using batteries from 16-19, the unit will de-rate according to the formula: P=Prating x N/20
*** If the UPS is installed or used in a place where the altitude is above than 1000m, the output must be derated one percent per 100m.
Product specifications are subject to change without further notice.